Remko WPM-Smart-Control-Manual for specialists-WKF-085 Manual de usuario Pagina 51

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 84
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 50
Hydraulic diagram for heat pump assembly WKF compact Stuttgart Solar
Functions: heating or cooling/hot water and solar, operating mode: monoenergetic
Only one cycle is possible for cooling; active cooling or floor heating (passive cooling)!
A
B
FBKKKW WW
ZK
S02
B
AB
A
Fig. 73: Example hydraulic diagram for HP assembly WKF compact Stuttgart Solar
A: Outdoor unit
B: WKF compact indoor unit
FB: Floor heating cycle
KK: Cooling cycle
KW: Cold water
WW: Hot water
ZK: Circulation
Menu item Parameter Factory setting
Control panel address Control panel 1-3 Control panel 1
Country Deutschland - Slovensko Deutschland
Load setting Accept the parameters Saving process
Language Deutsch - Polski Deutsch
Time zone Var. time zones possible Winter + 1(CET) (for Europe)
Date setting Year / Month / Day Current date setting
Time setting Hours / Minutes Current time setting
Activate heat pump Activated / Deactivated Activated
Operating mode
Monoenergetic / Bivalent
alternative
Monoenergetic / Enable as required
Domestic water heating Activated / Deactivated Activated
Storage tank set temperature "40°C - 65°C" 45°C
Hot water circulation Activated / Deactivated Deactivated
Circulation type Impulse or Temperature Impulse
51
Vista de pagina 50
1 2 ... 46 47 48 49 50 51 52 53 54 55 56 ... 83 84

Comentarios a estos manuales

Sin comentarios