Menu item Parameter Factory setting
Control panel address Control panel 1-3 Control panel 1
Country Deutschland - Slovensko Deutschland
Load setting Accept the parameters Saving process
Language Deutsch - Polski Deutsch
Time zone Var. time zones possible Winter + 1(CET) (for Europe)
Date setting Year / Month / Day Current date setting
Time setting Hours / Minutes Current time setting
Activate heat pump Activated / Deactivated Activated
Operating mode
Monoenergetic / Bivalent
alternative
Monoenergetic / Enable as required
Domestic water heating Activated / Deactivated Activated
Storage tank set temperature "40°C - 65°C" 45°C
Hot water circulation Activated / Deactivated Deactivated
Circulation type Impulse or Temperature Impulse
Circulation running time 1 min - 15 mins 5 mins
Disable switch-on 1 min - 15 mins 5 mins
Circulation type Impulse or Temperature Temperature
Circulation set temp. "25°C - 65°C" 35°C
Area-heating heating cycle Activated / Deactivated Following, as required
Area-heating heating cycle Deactivated No other parameters
Area-heating heating cycle Deactivated Parameter as required
Heating cycle mode Heating curve / Fixed value Heating curve
Heating-curve base point "15°C - 25°C" 20°C (or according to design)
Standard inlet temperature "28°C - 90°C" 35°C (or according to design)
Standard outside temperature "0°C - 20°C" According to design or locale
Standard inlet temperature "28°C - 90°C" 35°C (or according to design)
Standard outside temperature "0°C - 20°C" According to design or locale
Heating cycle radiators Activated / Deactivated As required
Heating cycle radiators Activated Following parameters, as required
Heating cycle mode Heating curve / Fixed value Heating curve
Heating-curve base point "15°C - 35°C" 20°C (or according to design)
Standard inlet temperature "40°C - 90°C" 45°C (or according to design)
Standard outside temperature "0°C - 20°C" According to design or locale
Building time constant "0 h - 100 h" 10 h
Standard heating load "0 kW - 25 kW"
According to design or heating load calcu-
lation