Hydraulic diagram for heat pump assembly WKF compact Mannheim bivalent
Functions: heating or cooling and hot water, operating mode: monoenergetic or bivalent alternative
Only one cycle is possible for cooling; active cooling or floor heating (passive cooling)!
The operating mode here can only be bivalent alternative!
A
B
C
D
HK
FB
KK
KW
WWZK
B
AB
A
HGU
Schema WKF_compact_Mannheim_bivalent_D_01_03
Fig. 71: Example hydraulic diagram for HP assembly WKF compact Mannheim bivalent
A: Outdoor unit
B: WKF compact indoor unit
C: Second heat generator (max. 20 kW)
D: Storage tank
FB: Floor heating cycle
HK: Heater heating cycle
KK: Cooling cycle
KW: Cold water
WW: Hot water
ZK: Circulation
Menu item Parameter Factory setting
Control panel address Control panel 1-3 Control panel 1
Country Deutschland - Slovensko Deutschland
Load setting Accept the parameters Saving process
Language Deutsch - Polski Deutsch
Time zone Var. time zones possible Winter + 1(CET) (for Europe)
Date setting Year / Month / Day Current date setting
Time setting Hours / Minutes Current time setting
Activate heat pump Activated / Deactivated Activated
Operating mode
Monoenergetic / Bivalent
alternative
Monoenergetic / Enable as required
Domestic water heating Activated / Deactivated Activated
Storage tank set temperature "40°C - 65°C" 45°C
Hot water circulation Activated / Deactivated Deactivated