Menu item Parameter Factory setting WKF
WKF
Duo
4th mixed heating cycle Activated / Deactivated Deactivated - X
Heating cycle mode Heating curve Deactivated - X
Heating-curve base point "15°C - 25°C" 20 °C - X
Standard inlet temperature "28°C - 90°C" 35 °C - X
Standard outside temp. "0°C - 20°C" 20 °C - X
System separation FBH Activated / Deactivated Deactivated X X
Setpoint increase 0 - 10 K 5.0 K X X
Building time constant "0 h - 100 h" 10 h X X
Standard heating load "0 kW - 25 kW" As required X X
Cooling function Activated / Deactivated Deactivated X X
Separate cooling cycle Activated / Deactivated Deactivated X X
Cooling via unmixed
heating cycle
Activated / Deactivated Deactivated X X
Solar plant Activated / Deactivated Deactivated X X
Pump type Asynchronous Deactivated X X
Asynchronous speed
control system
On / Off Deactivated X X
Pump type
EC pump
(high-efficiency pump)
Deactivated X X
Solar speed control syst. Activated / Deactivated Deactivated X X
Solar HM Deactivated Deactivated X X
Manual medium flow rate 2 l/min - 30 l/min 5.0 l/min X X
Medium flow rate probe 0 ml / lmp - 10 ml / lmp 5.7 ml / lmp X X
Heat carrier medium As required Tyfocor-L X X
Solar set temperature "5°C - 95°C" 85°C X X
Acquisition of the
stored energy
Activated / Deactivated Deactivated X X