Setting on SW2 System component Measuring range and description Unit
Heat exchanger temperature
sensor on the outdoor unit
(two-phase mixture) TH6
-39 – 88
-39 – +88
If the temperature sensor
measures values below 0°C,
the display switches between
the sign and the value.
°C
ON
1 2 3 4 5 6
Hot gas overheating tempera-
ture SHd
0 – 255
Cooling: TH4 - TH6
Heating: TH4 - TH5
0 – 255
If the temperature difference is
over 99 K, the display
switches between the 100s
digit and the 10s and 1s
digits.
K
ON
1 2 3 4 5 6
Cooling fin temperature sensor
TH8
-40 – 200
-40 – +200
If the temperature sensor
measures values below 0°C,
the display switches between
the sign and the value.
If the temperature is over
99°C, the display switches
between the 100s digit and the
10s and 1s digits.
°C
ON
1 2 3 4 5 6
Outdoor temperature TH7
-39 – 88
-39 – +88
If the temperature sensor
measures values below 0°C,
the display switches between
the sign and the value.
°C
ON
1 2 3 4 5 6
REMKO SYSTEM MONITOR
FOR REMKO SUPERTEC INVERTER
14