Issue D – U10REMKO GPMGas Wall HeaterOperation · Technology · Spare parts

Pagina 2

10REMKO GPMModulationThe gas wall heaters are units with flame modulation, whereby the widest range of outputs between the minimum and maximum settings

Pagina 3 - Contents

11Room correctionThe use of the electronic temperature regulation ATR-6 is required for this function. In the following, a type of function is describ

Pagina 4

12REMKO GPMInstructions for the userFault displaysA green and red LED are installed on the front of the unit.The illumination of the green LED means

Pagina 5 - Unit layout

13UnlockingWith malfunction of the fan-assisted air heater, it can be manually unlocked directly on the unit. There is a reset button for this purpose

Pagina 6

14REMKO GPMResetting the unitsThe malfunction (lock-out) of the unit is displayed by the appearance of a flashing triangle on the display of the electr

Pagina 7 - HW080909

15Operation and programming of the electronic temperature regulation ATR-6Operating mode With normal operating conditions the following information ap

Pagina 8

16REMKO GPMSetting the weekly timer Heating mode (HTG)With the key KM you arrive at page 1 of the menu. Now press key K1 (HTG) in order to select the

Pagina 9 - Reset button GREEN LED

17Programming of the HTG programming timer.With the key KM and then button K4 (>>) you arrive at page 2 of themenu.With the key K1 (PROG) the pr

Pagina 10

18REMKO GPMFrost protectionThis function always remains active when switching off through the operating unit.The fan-assisted heater switches on if th

Pagina 11 - Modulationstemperatur

19Automatic operationThe ventilation phase can also be operated automatically, where a weekly time programming is set, as described for heating.For us

Pagina 13 - Operation with electronic

20REMKO GPMBy pressing K1 (-), K2 (T1) or K3 (T2) the desired parameter that should be adjusted to the required time period is selected; the menu auto

Pagina 14

21The units are designed exclusively for heating and ventilation purposes in industrial or commercial use (no living space heating in private use) on

Pagina 15

22REMKO GPMThe following instructions for installation and set-up of the unitsare intended exclusively for authorised technicians.All safety notes mus

Pagina 16

23Pivoting wall installationThe instructions for installation of the pivoting brackets are included with the packaging.The use of pivoting brackets is

Pagina 17

24REMKO GPMHanging from the ceilingFor hanging the units by means of eyebolts, the Mounting set for ceiling installation with horizontal air outlet is

Pagina 18

25e.g. Gas fireplace type C:The combustion cycle is compact compared to the environment in which it is installed.The combustion air is fed from outside

Pagina 19

26REMKO GPMType B23 horizontalL1 maximum duct length without endpiecesØ 80 Ø 100Model MetresGPM15 29GPM25 29GPM35 26GPM55 15GPM 75 18Type B23 vertical

Pagina 20

27Type C13 horizontal / coaxialL1 + L2 maximum duct length without endpiecesØ 80 Ø 100Model MetresGPM15 10 + 10GPM25 10 + 10GPM35 10 + 10GPM55 4.5 + 4

Pagina 21

28REMKO GPMElectrical connectionThe electrical connection of the unit may only be carried out by authorised technicians (electrical power company-appr

Pagina 22 - 200 1000

29Gas connectionLEGEND1 = Electrical gas solenoid valve Main burner2 = Electrical gas solenoid valve Ignition burner3 = Pressure regulator4 = Ele

Pagina 23

3ContentsMade by REMKOThese operating instructions should be read carefully prior to commissioning / operation of the equipment!These instructions are

Pagina 24 - Hanging from the ceiling

30REMKO GPMCombustion analysisStart the burner and bring it up to "high output" after switching on the fan by holding the reset button on th

Pagina 25

31If the value lies beyond the indicated range, make adjustments with the CO2 regulating screw at the Venturi tube.- When tightening, the gas flow rat

Pagina 26

32REMKO GPMCountry Category Natural gas Pressure Liquid gas PressureATII2H3B/PG20 20 mbar G30/G31 50 mbarBE <70 kWI2E(S)B,I3PG20/G25 20/25 mbar G31

Pagina 27

33Check electrodes for their positioning according to instructions (see figure). It is important that the monitoring electrode [IO] lies tangential to

Pagina 28

34REMKO GPM7) Inspection of the ionisation currentCarry out the inspection with a tester that is capable of detecting microampere values with DC. -

Pagina 29 - 1 2 3 4 5 6 7 8

35The values that can be seen and adjusted with the electronic temperature regulation are found in the column PARAM K.NOTEWhen replacing the control P

Pagina 30

36REMKO GPMUnit without electronic temperature regulationWith replacement of the gas valve, the CO2 and, if applicable, the offset value must be adjus

Pagina 31

37The on-site conversion of the gas type may only be carried out by authorised, qualified technicians.Prior to the conversion, the country-specific requ

Pagina 32

38REMKO GPMPARAM KTSPFactory settingStandard Description1 A1 0 0 - 100 Minimum modulation value2 A2 0 0 - 100 Maximum modulation value3 A3 70 20 - 100

Pagina 33 - Maintenance

39Parameter PARAM KFor access to the PARAM K parameter, press the key KM (Menu) for approximately 8-10 seconds.The display shows:INFO REG ERR >&

Pagina 34

4REMKO GPMSafety notesThe units were subjected to extensive material, functional and quality inspections prior to delivery. However, dangers can emana

Pagina 35 - CR switch

40REMKO GPMFault-findingTroubleshootingJANEINJANEINJAJANEINNEINJAJaBETRIEB NORMALNEINSieheStörungs-ursachenGerätentriegelnGerätblockiertBlinktdieses

Pagina 36

41Type of faultsERRnur mit Temperatur-regelungF8F6F4F3F2F1Brenner zündet nichtSicherheitsthermostat (STB)Brennergebläse defektFühler NTC1 oder

Pagina 37

42REMKO GPM N L230V 50HzM1VA1VA2NLPENLPELEDNTCElectrical connection diagramLegend:ACF = Flame monitoring unitB1 = Ignition burner solenoid valve

Pagina 38

43When ordering spare parts, please state the computerised part no., unit number and type (see identification plate)!Exploded view366541329121413 7 811

Pagina 39

44REMKO GPM1621221819252928273132333424152320263017Venturi burnerWe reserve the right to modify the dimensions and constructional design as part of th

Pagina 40

45Spare parts listNo. Designation GPM15 GPM25 GPM35 GPM55 GPM 751 Control PCB 1110440 1110441 1110442 1110443 11104442 F1 Fuse 4A 1110445 1110445 111

Pagina 41 - Type of faults

46REMKO GPMUnit dimensionsSeries Dimensions Opening Suspended unit Gas supplyL B H V HB LB IM IS ID DM GAS GO GVGPM15 720 640 650 140 530 415 450 116

Pagina 42

47Technical dataSeries GPM15 GPM25 GPM35 GPM55 GPM 75min. max. min. max. min. max. min. max. min. max.Nominal thermal loadkW 12.5 16.5 20.0 26.5 24.0

Pagina 43 - Exploded view

REMKO ACROSS EUROPE… and in your area!Profit from our experience and adviceConsultancyIntensive training means our consultants are always up-to-date wi

Pagina 44

5Unit layoutOperating rangeModular systems can be created with the GPM-series gas wall heaters.Modular systems consist of one or multiple fan-assisted

Pagina 45 - Spare parts list

6REMKO GPMDescription of the unitDefinition of the equipmentPursuant to EU Directives, the equipment is defined as:"Gas fan-assisted air heater wit

Pagina 46

7The advantages of the units lie in the modular mode of operation, meaning the heat output created and thus the gas flow (consumption of fuel) are chan

Pagina 47 - Technical data

8REMKO GPMThe interruption of the current supply during burning operation is not permitted for the same reasons, because lack of a secondary ventilati

Pagina 48 - REMKO ACROSS EUROPE

9Faults FxThe control PCB mounted in the units differentiates between 6 different faults:F1 - Fault at the flame monitoring unit from loss of the flame